<2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default
setting shown is for V/f Control.
When using OLV Motor Control, leave the torque compensation gain (C4-01) at its default setting of 1.00. To increase
speed precision during regeneration in OLV Motor Control, enable slip compensation during regeneration (C3-04 = “1”).
u
Motor Hunting and Oscillation Control Parameters
In addition to the parameters discussed on page 162, the following parameters indirectly affect motor hunting and
oscillation.
Table 6.3
Parameters that Affect Control Performance in Applications
Name (Parameter No.) Application
Dwell Function (b6-01 through b6-04)
Prevents motor speed loss by maintaining the output frequency when working with heavy loads or when
there is powerful backlash on the machine side.
Accel/Decel Time (C1-01 through
C1-09)
Adjusting accel and decel times will affect the torque presented to the motor during acceleration or
deceleration.
S-Curve Characteristics (C2-01
through C2-04)
Prevents shock at the beginning and end of acceleration and deceleration.
Jump Frequency (d3-01 through d3-04) Skips over the resonant frequencies of connected machinery.
Analog Filter Time Constant (H3-13) Prevents fluctuation in the analog input signal due to noise.
Stall Prevention (L3-01 through L3-06,
L3-11)
• Prevents motor speed loss and overvoltage. Used when the load is too heavy and also during sudden
acceleration/deceleration.
• Adjustment is not normally required because Stall Prevention is enabled as a default. Disable Stall
Prevention during deceleration (L3-04 = “0”) when using a braking resistor.
Torque Limits (L7-01 through L7-04,
L7-06, L7-07)
• Sets the maximum torque for Open Loop Vector Control.
• Ensure that the drive capacity is greater than the motor capacity when increasing this setting. Be careful
when reducing this value because motor speed loss may occur with heavy loads.