5.1 A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.
u
A1: Initialization
n
A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No. Parameter Name Setting Range Default
A1-00 Language Selection 0 to 7
<1>
<1> Regional default settings:
Setting 0: Japan (Model code: CIMR-VAoA) and Asia (Model code: CIMR-VToA)
Setting 7: China (Model code: CIMR-VBoA)
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
n
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No. Parameter Name Setting Range Default
A1-01 Access Level Selection 0 to 2 2
Setting 0: Operation Only
Access is restricted to parameters A1-01, A1-04, A1-06, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters
set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Notes on Parameter Access
If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all
A2 parameters cannot be modified.
If a digital input programmed for Program Lockout (H1-oo = 1B) is enabled, parameter values can not be modified,
even though the A1-01 is set to 1 or 2.
If parameters are changed via serial communication the parameters can not be changed from the digital operator until
an Enter command is received from the serial communication.
n
A1-02: Control Method Selection
Selects the Control Method of the drive.
Note: 1. Be sure to perform Auto-Tuning when using one of the vector control modes.
2. Reinitializing the drive does not reset A1-02 to the factory default value.
No. Parameter Name Setting Range Default
A1-02 Control Method Selection 0, 2, 5 0
Setting 0: V/f Control
For general-purpose and multiple motor applications.
For use when the motor parameters are unknown and Auto-tuning can not be performed.
5.1 A: Initialization
112
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20