n
F1-14: PG Open-Circuit Detection Time
Sets the time required to detect PGo if no pulse signal is present at terminal RP.
No. Parameter Name Setting Range Default
F1-14 PG Open-Circuit Detection Time 0.0 to 10.0 s 2.0 s
u
F6: Serial Communications Option Card Settings
These parameters configure communication option cards and communication fault detection methods.
n
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
No. Parameter Name Setting Range Default
F6-01 Communications Error Operation Selection 0 to 3 1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No. Parameter Name Setting Range Default
F6-02 External Fault from Comm. Option Selection 0 or 1 0
Setting 0: Always Detected
Setting 1: Detection During Run Only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No. Parameter Name Setting Range Default
F6-03 External Fault from Comm. Option Operation Selection 0 to 3 1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-07: NetRef/ComRef Function Selection
Selects how multi-step speed inputs are treated when the NetRef command is set.
No. Parameter Name Setting Range Default
F6-07 NetRef/ComRef Function Selection 0 or 1 0
Setting 0: Multi-Step Speed Operation Disabled
If the NetRef command is selected, multi-step speed
input frequency references are disabled. This is the same as Yaskawa
F7 drives.
Setting 1: Multi-Step Speed Operation Enabled
Multi-step speed inputs are active and can override the frequency reference from the communications option even when
the NetRef command is selected. This is the same as Yaskawa F7 drives.
5.6 F: Option Settings
174
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20