o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when the power is cycled or the drive is initialized. o4-12 can be
used to manually reset them.
No. Name Setting Range Default
o4-12 kWh Monitor Initialization 0 or 1 0
Setting 0: No Action
The kWh data are kept as they are.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and
U4-11 will show 0. Once o4-12 is set to 1 and the ENTER key is pressed,
the kWh data are erased and the display returns to 0.
n
o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Using o4-13
it can be manually reset to 0.
No. Name Setting Range Default
o4-13 Number of Run Commands Counter Reset 0 or 1 0
Setting 0: No Action
The Run command data are kept as they are.
Setting 1: Reset Run Commands Counter
Resets the Run commands counter. The monitor U4-02
will show 0. Once o4-13 is set to 1 and the ENTER key is pressed,
the counter value is erased and the display returns to 0.
u
q: DriveWorksEZ Parameters
n
q1-01 to q6-07: Reserved for Use by DriveWorksEZ
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
u
r: DriveWorksEZ Connection Parameters
n
r1-01 to r1-40: DriveWorksEZ Connection Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
u
T: Motor Tuning
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.
Refer to Auto-Tuning on page 100 for details on Auto-Tuning parameters.
5.10 o: Operator Related Settings
240
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20