n
PID Block Diagram
-
+
+
+
+
+
+
+
+
+
+
+
+
-
+
-
+
+
+
+
+
Frequency
Reference 1
Frequency Reference 1 to 16
Option Card
Serial Comm
Analog Input A1/A2
Pulse Input
b1-01
PID disable when:
- b5-01=0
- a JOG Command is Input
- PID Disable by Digital Input Enabled
PID Block Diagram
d1-01 to d1-16
1
2
3
0
PID Target
PID Soft
Starter b5-17
PID SFS Cancel DI
H1-oo=34
4
b5-01
1/2
3/4
1/2
3/4
0
Off
On
not 1
PID Set Point
(U5-04)
b5-18=1
0
Reg. 0Fh, bit 1
PID Feedback
PID Feedback
(U5-01)
H6-01=2
H3-02/10=C
H6-01=1
not B
not C
not 2
not 1
H3-02/10=B
Analog Input A1/A2
Pulse Input
MEMOBUS Reg. 0006h
b5-19
0
1
Analog Input A1/A2
Pulse Input
0
PID Input
(U5-02)
b5-05
b5-01
2 or 4
1 or 3
PID Input
Limit
b5-35
Analog Input A1/A2
0
not 16
H3-02/10
= 16
PID Differential
Feedback
(U5-05)
Adjusted
PID Feedback
(U5-06)
Derivative
Time
Proportional
Gain
b5-02
I-time
b5-03
Integral Hold
H1-oo=31
1
0
PID Input
Characteristic
H1-oo=35
1
0
Derivative
Time
PID Ouput
(U5-03)
b5-08
I - limit
b5-04
PID Output
Upper/Lower
Limit
b5-06 / b5-34
PID Delay
Time
Integral Reset
H1-oo=30
PID Output
Characteristic
b5-09
1 or 3
2 or 4
b5-01
Disabled
Enabled
Upper Limit
Fmax x109%
Lower Limit
Fmax x109%
Lower Limit 0
Upper Limit
Fmax x109%
1
Output
Frequency
Enable / Disable Reverse
Operation when PID
Output is Negative
0
b5-07
b5-10
PID Output
Gain
PID Offset
b5-15
Sleep Level
RUN
On/Off
Delay
Timer
Sleep Function
SFS
C1-oo
b5-11
1
0
Always 1 when
b5-01 = 3/4
b5-16
1/s
-1
Z
-1
Z
-1
-1
Z
-1
P
1
0
PID SFS Cancel DI
H1-oo=34
b5-05
Figure 5.17 PID Block Diagram
5.2 b: Application
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
133
5
Parameter Details

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20