Table 5.19 Rated Output Operation, Settings C to F
Setting = C 90 Hz Setting = D 120 Hz Setting = E 180 Hz Setting = F 60 Hz
0
12
16
200
1.5 3 9060
Voltage (V)
Frequency (Hz)
0
12
16
200
1.5 3 12060
Voltage (V)
Frequency (Hz)
0
12
16
200
1.5 3 18060
Voltage (V)
Frequency (Hz)
0
12
16
200
1.5 3 60
Voltage (V)
Frequency (Hz)
Predefined V/f Patterns for 5.5 to 18.5 kW Drives
The following graphs are for 200 V class drives. Double values when using a 400 V class drive.
Table 5.20
Rated Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3
72 Hz
0
7
200
1.3 2.5 50
14
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3 60
Voltage (V)
Frequency (Hz)
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3 6050
0
7
14
200
1.5 3 7260
Voltage (V)
Frequency (Hz)
Table 5.21 Derated Torque Characteristics, Settings 4 to 7
Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 Hz
Voltage (V)
Frequency (Hz)
0
6
200
1.3 25 50
35
0
7
200
1.3 25 50
50
Voltage (V)
Frequency (Hz)
Voltage (V)
Frequency (Hz)
0
6
200
1.5 30 60
35
0
7
200
1.5 30 60
50
Voltage (V)
Frequency (Hz)
Table 5.22 High Starting Torque, Settings 8 to B
Setting = 8 50 Hz Setting = 9 50 Hz Setting = A 60 Hz Setting = B 60 Hz
0
9
200
1.3 2.5 50
18
Voltage (V)
Frequency (Hz)
Voltage (V)
Frequency (Hz)
0
11
200
1.3 2.5 50
23
Voltage (V)
Frequency (Hz)
0
9
200
1.5 3 60
18
0
13
200
1.5 3 60
23
Voltage (V)
Frequency (Hz)
Table 5.23 Constant Output, Settings C to F
Setting = C 90 Hz Setting = D 120 Hz Setting = E 180 Hz Setting = F 60 Hz
0
7
14
200
1.5 3 9060
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3 12060
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3 18060
Voltage (V)
Frequency (Hz)
Voltage (V)
Frequency (Hz)
0
7
14
200
1.5 3 60
Setting a Custom V/f Pattern
Setting parameter E1-03 to “F” allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When E1-03 is changed to “F”, the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 1 of the
predefined patterns.
5.5 E: Motor Parameters
164
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20