EasyManuals Logo

YASKAWA V1000 Technical Manual

YASKAWA V1000
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #388 background imageLoading...
Page #388 background image
No. Description Unit Setting Range
Model 4A0007 4A0009 4A0011 4A0018
o2-04 Drive Model Selection 95 96 97 99
C6-01 Normal/Heavy Duty
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
E2-11
(E4-11,
T1-02)
Motor rated power kW 2.2 3.0 3.0 3.7 4.0 5.5 5.5 7.5
b3-06 Speed Search current 1 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed
Search (Speed Estimation Type)
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy saving coefficient 313.6 265.7 265.7 245.8 245.8 189.5 189.5 145.38
C6-02 Carrier frequency 3 7 3 7 3 7 3 7
E2-01
(E4-01,
T1-04)
Motor rated current A 4.2 5.7 5.7 7 7 9.8 9.8 13.30
E2-02
(E4-02)
Motor rated slip Hz 3 2.7 2.7 2.7 2.7 1.5 1.5 1.3
E2-03
(E4-03)
Motor no-load current A 1.5 1.9 1.9 2.3 2.3 2.6 2.6 4.0
E2-05
(E4-05)
Motor line-to-line resistance Ω 6.495 4.360 4.360 3.333 3.333 1.595 1.595 1.152
E2-06
(E4-06)
Motor leakage inductance % 18.7 19 19 19.3 19.3 18.2 18.2 15.5
E2-10
(E4-10)
Motor Iron Loss W 77 105 105 130 130 193 193 263
E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Momentary power loss ride-
through time
s 0.5 0.5 0.5 0.5 0.5 0.5 0.8 0.8
L2-03
Momentary power loss Baseblock
time
s 0.5 0.5 0.5 0.6 0.6 0.7 0.7 0.8
L2-04
Momentary power loss voltage
recovery time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05 Uv detection voltage V dc 380 380 380 380 380 380 380 380
L3-24 Motor acceleration time s 0.145 0.145 0.145 0.154 0.154 0.154 0.168 0.175
L8-02 Overheat alarm level °C 100 100 100 100 100 100 110 110
L8-09 Ground fault selection 0 0 0 0 0 0 1 1
L8-35 Installation Method Sel. 0 0 0 0 0 0 2 2
L8-38
Carrier frequency reduction
selection
1 1 1 1 1 1 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n2-01
Speed Feedback Detection Control
(AFR) Gain
1.00 1.00 1.00 1.00 1.00 1.00 1.50 1.50
B.6 Defaults by Drive Model and Duty Rating (ND/HD)
388
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20