Page #100 background imageLoading...
Page #100 background image
<5. Functions>
99
IM 01E21A02-03EN
5.6.3 Operation at the Time of Error
The following table shows outputs at the time of error and actions of the outputs.
■Systemalarm
Error XD_ERROR BLOCK_ERR
Process
value*
Totalizer Display
No Message STB DTB MTB LTB STB DTB MTB LTB
10 Main CPU FAIL 20 -- -- -- Other -- -- -- STOP Totalizer stop Undened
11
Reverse
calculation failure
20 -- -- -- Other -- -- --
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
12
Main board
EEPROM failure
23 -- -- -- Other -- -- --
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
13
Main board
EEPROM default
17 -- -- -- Other -- -- --
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
14
Sensor board
failure
20 -- -- -- Other -- -- --
Hold Prior
setting
Follows
settings(see
4.2.4).
Alarm
15
Sensor
communication
error
20 -- -- -- Other -- -- --
Hold Prior
setting
Follows
settings(see
4.2.4).
Alarm
16
A/D1
failure[Signal]
20 -- -- -- Other -- -- --
Hold Prior
setting
Follows
settings(see
4.2.4).
Alarm
17
A/D2
failure[Exciter]
20 -- -- -- Other -- -- --
Hold Prior
setting
Follows
settings(see
4.2.4).
Alarm
18 Coil open 17 -- -- -- Other -- -- --
Hold Prior
setting
Follows
settings(see
4.2.4).
Alarm
19 Coil short 20 -- -- -- Other -- -- --
Hold Prior
setting
Follows
settings(see
4.2.4).
Alarm
20 Exciter failure 20 -- -- -- Other -- -- --
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
27
Parameter restore
incomplete
-- -- 17 -- -- -- Other --
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
28
Indicator board
failure
-- -- -- 20 -- -- -- Other
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
29
Indicator board
EEPROM failure
-- -- -- 23 -- -- -- Other
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
30 LCD driver failure -- -- -- 20 -- -- -- Other
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
31
Indicator board
mismatch
-- -- -- 20 -- -- -- Other
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
32
Indicator
communication
error
-- -- -- 20 -- -- -- Other
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
33 microSD failure -- -- -- 20 -- -- -- Other
Normal
calculation
Follows
settings(see
4.2.4).
Alarm
244
Amp EEPROM
Failure
-- -- -- -- -- -- -- -- -- -- Alarm
249
SoftDL
Incomplete
-- -- 17 -- -- -- Other -- -- -- Alarm
250 SoftDL Failure -- -- 17 -- -- -- Other -- -- -- Alarm

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals