<5. Functions>
107
IM 01E21A02-03EN
5.6.6 Alarm Mask Function
Thealarmmaskfunctioncanmaskaspeciedalarm,hideanalarmnotication,andrecordno
alarmhistory.Themaskfunctioncanbesetforboththealarmnoticationandalarmrecord,
respectively. This function is only for alarm whose FD is 2, 3, 4 or 5 in the Alarm List, 5.6.2 Errors
and Countermeasures. Only this target alarm is described below.
Thesettingcanbeconguredwiththefollowingparameters.
Alarmnoticationmask
Ifthealarmnoticationmaskfunctionisturned“On”,itdisablesalarmnotication.
Settingexampleforalarm“Signaloverow”:
Todisablethealarmnotication,set“Signaloverow”ofSTB:AlarmOutMask2to“On”.
Toenablethealarmnotication,set“Signaloverow”ofSTB:AlarmOutMask2to“O”.
Menu path
Display Devicesetup►Diag/Service►Sts/Selftest►Alarm►Alarmoutmask►(seebelow)
F
OUNDATION
Fieldbus
Diagnostic►STB►DeviceDiagnostics►Diagnostics/Alerts►Alert►AlarmOutMask
►(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
STB 148
Mask 1-1
Alarm Out Mask1
Speciesthemaskfunctionfor
alarmnotication1-1.
Mask 1-2
Speciesthemaskfunctionfor
alarmnotication1-2.
STB 149
Mask 2-1
Alarm Out Mask2
Speciesthemaskfunctionfor
alarmnotication2-1.
Mask 2-2
Speciesthemaskfunctionfor
alarmnotication2-2.
STB 150
Mask 3-1
Alarm Out Mask3
Speciesthemaskfunctionfor
alarmnotication3-1.
Mask 3-2
Speciesthemaskfunctionfor
alarmnotication3-2.
STB 151 Mask 4-1 Alarm Out Mask4
Speciesthemaskfunctionfor
alarmnotication4-1.