<3. Getting Started>
20
IM 01E21A02-03EN
3.4 Integration of DD
IfthehostsupportsDD(DeviceDescription),theDDofthisproductneedstobespecied.Check
if the host has the following directory under the directory to specify DD.
594543¥0016(AXG)
594543¥0017(AXW)
 (594543isthemanufacturernumberofYokogawaElectricCorporation,and0016is
thedevicenumberofAXG,and0017isthedevicetypeforAXW.)
If the directory is not found, the DD of this product has not been included. Create the above
directoryandcopytheDDleofthisproduct(0m0n.󰀨5,0m0n.sy5(m,nisanumeral))
(separatelysupplied)intothedirectory.
Here,’0m’inthelenameshowsthedevicerevision,and’0n’showstheDDrevision.
Once the DD is installed in the directory, the name and attribute of all parameters of this product
are displayed.
Also,o󰀨-linecongurationispossiblebyusingcapabilitiesles(CFF).
IfyoudonothavetheDDorcapabilitiesles,youcandownloadthemfromYokogawa’sweb
page: Access the following web site, or contact your sales agent where you purchased this
product.
http://www.yokogawa.com/d/doc/
3.5 Reading the Parameters
Select the AI block of this product from the host screen, and read the OUT parameter. The
measuredvalueassignedtothepresentAIisdisplayed.CheckthatMODE_BLKofthefunction
block and resource block is set to AUTO, change the input signal being measured, and read the
parameter again. A new designated value will be displayed.
3.6 Continuous Record of Values
If the host has a function that continuously records the indications, use the function to record the
indications(values).Dependingonthehostbeingused,itisnecessarytosetthescheduleof
Publish(functiontotransmittheindicationtothebusonaperiodicbasis).
3.7 Generation of Alarm
Theblockalarm,out-of-rangealarmoftheoutputparameter(OUT)andupdatealarmatsetting
change can be generated from this product. When generating alarm, a Link Object and a VCR
Static Entry need to be set. For details of Link Object and VCR Static Entry, refer to Subsection
4.6.1 Link object and Subsection 4.5.1 VCR Setting.