5.11.4 Data Logging Function
WhentheoptionalcodeMC(microSDcard)isselected,thedataloggingfunctioncanstoreup
tofourprocessvaluestothemicroSDcard.Tousethisfunction,itisnecessarytospecifyale
name, data storage interval,and ending time.
Storeddataissavedinthe“YOKOGAWA”folderasa“.TRD”le.
Thesettingcanbeconguredwiththefollowingparameters.
Menu path
Display Devicesetup►Diag/Service►Datalog►(seebelow)
F
OUNDATION
Fieldbus
DeviceConguration►MTB►DeviceConguration►Maintenance►DataLogging►
(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
MTB 85 File name Logging File Name
Speciesthenameoftheletobe
stored.
MTB 86 Interval time Logging Interval Time
Speciesthedatastorage
interval.
*1
MTB 87 Start date Logging Start Date
Displays the date to start the data
logging function.
MTB 88 Start time Logging Start Time
Displays the time to start the data
logging function.
MTB 89 End time Logging End Time
Speciesthetimetoendthedata
logging function.
*2
MTB 90 Log 1 Log 1 Select
Speciesprocessvalue1tobe
stored.
*3
MTB 91 Log 2 Log 2 Select
Speciesprocessvalue2tobe
stored.
*3
MTB 92 Log 3 Log 3 Select
Speciesprocessvalue3tobe
stored.
*3
MTB 93 Log 4 Log 4 Select
Speciesprocessvalue4tobe
stored.
*3
MTB 94 Execute Logging Execute
Speciestheexecutionofthedata
logging function.
*4
*1: From the table below, select the data storage interval.
Selection
Description
Display
F
OUNDATION
Fieldbus
1 s 1s Sets the storage interval to 1 sec.
10 s 10s Sets the storage interval to 10 sec.
30 s 30s Sets the storage interval to 30 sec.
1 min 1min Sets the storage interval to 1 min.
5 min 5min Sets the storage interval to 5 min.
30 min 30min Sets the storage interval to 30 min.
1 h 1h Sets the storage interval to 1 hour.

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals