<Appendix 1. Application, Setting And Change Of Basic Parameters>
236
IM 01E21A02-03EN
Appendix 1. Application, Setting and
Change of Basic Parameters
A1.1 Applications and Selection of Basic
Parameters
Setting Item (applicable
parameter)
Overview
TagNo.(PD_TAG)setup
Sets PD_TAG and each block tag.
Up to 32 alphanumeric characters can be set for both.
Calibration range setup
(XD_SCALEofAIblock)
Sets the range of input from the transducer block corresponding to 0% point
(always0forthisproduct)and100%pointsinoperationwithintheAIfunction
block.“Spanowrate”,itemspeciedatordering,issetatfactoryshipping.
Setsthefollowingfourdata;arangeunit,inputvalueofthe0%point(incase
ofthisproduct,0),inputvalueofthe100%point(correspondingtoowrate
span)anddecimal-pointposition.
Output scale setup
(OUT_SCALEofAIblock)
The same value as XD_SCALE is set at shipment from the manufacturing
factory.
Simulation setup
(SIMULATEofAI/DIblock)
Performs simulation of the AI/DI function block.
The input value and status for the calibration range can also be set. Use this
parameterforloopcheckandotherpurposes.Referto“SimulationFunction”
in Section 5.13.
Damping time constant setup
(PRIMARY_VALUE_FTIMEof
STB)
Sets the damping time constant in seconds. The setting of PRIMARY_
VALUE_FTIMEa󰀨ectsnotonlytheowrate,butalsothetotalization.
In comparison, the setting of parameter PV_FTIME in an AI function
block works as the damping time constant for the AI block’s OUT.
Asthedampingfunctionoftheowmeteritself,itisadvisabletouse
PRIMARY_VALUE_FTIME.
Output signal low cut mode
setup
(PRIMARY_VALUE_LOWCUT
ofSTB)
Thissetupisusedforzeroingowratereadingsinalowowratearea.
SpeciesthevalueofPRIMARY_VALUE_LOWCUTasapercentof
PRIMARY_VALUE_RANGE. In comparison, the setting of parameter
LOW_CUTintheAIfunctionblockworksasalowcuto󰀨levelsettingforthe
AIblock’sOUT.Asthelow-cutfunctionoftheowmeteritself,itisadvisable
to use PRIMARY_VALUE_LOWCUT.
LCD display setup
(DISPLAY_SELECT1-3,
DISPLAY_CYCLEofSTB)
Sets the type of data, the unit to be displayed on the LCD and the display
speed.
Adjust display speed if a low temperature environment causes a poor LCD
display quality.
Zero adjustment
(AUTO_ZERO_EXE,MAGFLO_
ZEROofSTB)
Performs zero adjustment. Zero adjustment should be done only when the
measurementuidislledinthesensorandtheuidvelocityiscompletely
zero.

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals