<Appendix 5. PID Block>
286
IM 01E21A02-03EN
Note 2: A transition to Cas, RCas, or ROut requires that initialization of the cascade connection
has been completed.
Note3:Incaseofthemodeshedding(thedatastatusofRCAS_IN,ROUT_INisBAD),it
transitionstothemodewhichhasbeenspeciedwithSHED_OPT.(Fordetails,referto
A5.17.1.)
A5.10 Bumpless Switching
BumplessswitchingisthefunctiontoallowthebumplessswitchofMODE_BLKandofoperation
output values at the cascade downstream without a sudden change in the control output.
Theactiontoperformabumplessswitchingdi󰀨ersdependingontheMODE_BLKvalues.
A5.11 Setpoint Limiter
Thesetpointlimiterfunctionistolimitthesettingsofthesetpoint(SP).
Theoperationofthesetpointlimiterdi󰀨ersbasedontheblockmodeofthefunctionblock.
A5.11.1 When PID Block Is in Auto Mode
Whentheblockmode(MODE_BLK)isAuto,thelimitersofthesetpoint(SP)inforcearehigh/low
limit and change-rate limit.
A5.11.1.1 High/Low Limit
Avalueexceedingthesethighlimit(SP_HI_LIM)cannotbesetforSP.
Avaluesmallerthanthesetlowlimit(SP_LO_LIM)cannotbesetforSP.
A5.11.1.2 Change-rate Limit
The change-rate limits are used to restrict the magnitude of changes in the SP value so as to
change the SP value gradually towards a new setpoint.
TheincreaseoftheSPvalueateachexecutionperiodofPID(periodofexecutionintheBlock
Header)islimitedtothevalueofSP_RATE_UPorless.
ThedecreaseoftheSPvalueateachexecutionperiodofPID(periodofexecutionintheBlock
Header)islimitedtothevalueofSP_RATE_DOWNorless.
A5.11.2 When PID Block Is in Cas or RCas Mode
ByselectingObeySPLimitsifCasorRCasinCONTROL_OPTS(seeSubsectionA5.13.1),the
setpoint(SP)high/lowlimitscanbeputintoforcewhentheblockmode(MODE_BLK)isCasor
RCas.

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals