EasyManuals Logo

YOKOGAWA ADMAG TI Series User Manual

YOKOGAWA ADMAG TI Series
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #241 background imageLoading...
Page #241 background image
<Appendix 1. Application, Setting And Change Of Basic Parameters>
240
IM 01E21A02-03EN
Resetting or presetting totalized value
Reset totalization
AccesstheOP_CMD_INTparameterinITblock,andsetReset“1”.
Preset totalization
(1) AccesstheMODE_BLKparameterintheITblockandsetTarget(targetmode)toO/Sor
Man in.
(2) AccesstheOUTparameterintheITblock,andsetpresetvalueto“Value”.
(3) AccesstheMODE_BLKparameterintheITblockandsetTarget(targetmode)toAuto.
A1.5 Setting the DI Function Block
The DI function block receives and outputs limit switch signals from the transducer block.
Three DI blocks have independent parameters. Set up the parameters of each DI block you use,
individually as necessary. The following shows setting examples of the DI1 function block.
Setting the channel
SpeciesthelimitswitchnumberofthetransducerblocktobeinputtotheDIblock.Fordetails,
refer to Section 5.3.
Setting the damping time constant
AccessthePV_FTIMEparameter.Setatimetodamp.(inunitsofseconds)
Simulation
Perform simulation of each DI function block by setting the desired value and status of the input
to the block. Access the SIMULATE_D parameter and change the values of its elements as
follows.
(1) REMOTELOOPTESTSWITCHiswrittentotheSIM_ENABLE_MSG(index2922)
parameter of the MTB.
(2) AccesstheSIMULATE_DEn/Disableparameter.Setthesimulationactiveordisable.
2 : Active
1 : Disable
(3) AccesstheSIMULATE_DStatusparameter.Setthedesiredstatuscode.
(4) AccesstheSIMULATE_DValueparameter.Setthedesiredinputvalue.
When valid, the DI block uses SIMULATE_D Status and SIMULATE_D Value as an input, and
when invalid, the DI block uses Transducer Status and Transducer Value as an input. Refer to
“SimulationFunction”inSection5.13.

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?