<Appendix 1. Application, Setting And Change Of Basic Parameters>
239
IM 01E21A02-03EN
(3)AccesstheSIMULATEstatusparameter.Setthedesiredstatuscode.
(4)AccesstheSIMULATEvalueparameter.Setthedesiredinputvalue.
If simulation is enabled, AI block uses SIMULATE Status and SIMULATE Value as the input,
and if disabled, the AI block uses Transducer Status and Transducer Value as input. Refer to
“SimulationFunction”inSection5.13.
A1.4 Setting the Integrator (IT) Function Block
TheITfunctionblockoutputstheowratetotalization.
Settingtheunitofowratetotalization
(1) AccesstheTIME_UNIT1parameterinITblockandsettheRATEtimeunitcorresponding
IN_1.(IfthereexistsinputtoIN_2,settheRATEtimeunitinTIME_UNIT2inthesameway.)
(2) AccesstheOUT_RANGEparameteroftheITblock,andsettheFlowrateunitto“Units
Index”.
Settingtheforward/reversedirectionoftheowratetotalization
AccesstheINTEG_OPTSparameterinITblock,andset0or1to“Bit#2”or“Bit#3”.
(Example1) Forwardowtotalization
Bit#2=1
Bit#3=0
(Example2) Reverseowtotalization
Bit#2=0
Bit#3=1
(Example3) Dierentialowratetotalization
Bit#2=1
Bit#3=1