<Appendix 1. Application, Setting And Change Of Basic Parameters>
239
IM 01E21A02-03EN
(3)AccesstheSIMULATEstatusparameter.Setthedesiredstatuscode.
(4)AccesstheSIMULATEvalueparameter.Setthedesiredinputvalue.
If simulation is enabled, AI block uses SIMULATE Status and SIMULATE Value as the input,
and if disabled, the AI block uses Transducer Status and Transducer Value as input. Refer to
“SimulationFunction”inSection5.13.
A1.4 Setting the Integrator (IT) Function Block
TheITfunctionblockoutputstheowratetotalization.
Settingtheunitofowratetotalization
(1) AccesstheTIME_UNIT1parameterinITblockandsettheRATEtimeunitcorresponding
IN_1.(IfthereexistsinputtoIN_2,settheRATEtimeunitinTIME_UNIT2inthesameway.)
(2) AccesstheOUT_RANGEparameteroftheITblock,andsettheFlowrateunitto“Units
Index”.
Settingtheforward/reversedirectionoftheowratetotalization
AccesstheINTEG_OPTSparameterinITblock,andset0or1to“Bit#2”or“Bit#3”.
(Example1) Forwardowtotalization
Bit#2=1
Bit#3=0
(Example2) Reverseowtotalization
Bit#2=0
Bit#3=1
(Example3) Di󰀨erentialowratetotalization
Bit#2=1
Bit#3=1

Table of Contents