EasyManuals Logo

YOKOGAWA ADMAG TI Series User Manual

YOKOGAWA ADMAG TI Series
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #240 background imageLoading...
Page #240 background image
<Appendix 1. Application, Setting And Change Of Basic Parameters>
239
IM 01E21A02-03EN
(3)AccesstheSIMULATEstatusparameter.Setthedesiredstatuscode.
(4)AccesstheSIMULATEvalueparameter.Setthedesiredinputvalue.
If simulation is enabled, AI block uses SIMULATE Status and SIMULATE Value as the input,
and if disabled, the AI block uses Transducer Status and Transducer Value as input. Refer to
“SimulationFunction”inSection5.13.
A1.4 Setting the Integrator (IT) Function Block
TheITfunctionblockoutputstheowratetotalization.
Settingtheunitofowratetotalization
(1) AccesstheTIME_UNIT1parameterinITblockandsettheRATEtimeunitcorresponding
IN_1.(IfthereexistsinputtoIN_2,settheRATEtimeunitinTIME_UNIT2inthesameway.)
(2) AccesstheOUT_RANGEparameteroftheITblock,andsettheFlowrateunitto“Units
Index”.
Settingtheforward/reversedirectionoftheowratetotalization
AccesstheINTEG_OPTSparameterinITblock,andset0or1to“Bit#2”or“Bit#3”.
(Example1) Forwardowtotalization
Bit#2=1
Bit#3=0
(Example2) Reverseowtotalization
Bit#2=0
Bit#3=1
(Example3) Di󰀨erentialowratetotalization
Bit#2=1
Bit#3=1

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals