<5. Functions>
168
IM 01E21A02-03EN
5.14.6 Frequency Output Range Setting
Whenthefrequencyoutputisused,thefrequencyat0%and100%canbespeciedforthespan
of the process value. The frequency output range can be set by specifying the frequency.
Set the output frequency for the span of the process value which is assigned to PV in Subsection
5.1.2.
Thesettingcanbeconguredwiththefollowingparameters.
Menu path
Display Devicesetup►Detailedsetup►Pulse/Statusout►PO1/SO1►(seebelow)
F
OUNDATION
Fieldbus
DeviceConguration►MTB►DeviceConguration►Maintenance►Pulse/StatusOut
►(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
MTB 110 Frequency at 0% Frequency 1 at 0%
Speciestheoutputfrequency
when the process value is 0%.
MTB 111 Frequency at 100% Frequency 1 at 100%
Speciestheoutputfrequency
when the process value is
100%.
5.14.7 Status Output Function Setting
When the status output is used, the device status can be output as a contact point.
Thesettingcanbeconguredwiththefollowingparameter.
Menu path
Display Devicesetup►Detailedsetup►Pulse/Statusout►PO1/SO1►(seebelow)
F
OUNDATION
Fieldbus
DeviceConguration►MTB►DeviceConguration►Maintenance►Pulse/StatusOut
►(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
MTB 112 SO1 function SO1 Function
Speciesthestatusoutput
function.
From the table below, select the status output function.
Selection
Description
Display
F
OUNDATION
Fieldbus
No function No function
The status output is not available because the status output function is
not enabled.
Alarm output Alarm output Thestatusoutputisactivatedwhenthespecicalarmoccurs.
Warning output Warning output Thestatusoutputisactivatedwhenthespecicwarningoccurs.
Total limit 1 Total limit 1
The status output is activated while the totalized value of totalizer 1
is out of the set target value. For details about the totalization switch
function, refer to Subsection 5.2.3.
Total limit 2 Total limit 2
The status output is activated while the totalized value of totalizer 2
is out of the set target value. For details about the totalization switch
function, refer to Subsection 5.2.3.

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals