<Appendix 5. PID Block>
291
IM 01E21A02-03EN
A5.17.1 SHED_OPT
TheSHED_OPTsettingstipulatesthespecicationsofmodeshedding.
Available Setting for
SHED_OPT
Operation Contents
Normal shed, normal return SetsMODE_BLK.actualtoCas(*1),andleavesMODE_BLK.targetunchanged.
Normal shed, no return SetsbothMODE_BLK.ActualandMODE_BLK.TargettoCas(*1).
Shed to Auto, normal return SetsMODE_BLK.actualtoAuto(*2),andleavesMODE_BLK.targetunchanged.
Shed to Auto, no return SetsbothMODE_BLK.actualandMODE_BLK.targettoAuto(*2).
Shed to Manual, normal
return
SetsMODE_BLK.actualtoMan,andleavesMODE_BLK.targetunchanged.
Shed to Manual, no return SetsbothMODE_BLK.actualandMODE_BLK.targettoMan.
Shed to retained target,
normal return
1. IfCasisspeciedinMODE_BLK.target,setsMODE_BLK.actualtoCas(*1),
andleavesMODE_BLK.targetunchanged.
2. IfCasisnotspeciedinMODE_BLK.target,setsMODE_BLK.actualto
Auto(*2),andleavesMODE_BLK.targetunchanged.
Shed to retained target, no
return
1. IfCasisspeciedinMODE_BLK.target,setsbothMODE_BLK.Actualand
MODE_BLK.TargettoCas(*1).
2. IfCasisnotspeciedinMODE_BLK.target,setsMODE_BLK.actualto
Auto(*2),andMODE_BLK.targettoCas.
ThemodestowhichaPIDblockcantransferarelimitedtothosespeciedinMODE_BLK.
permitted.
The priority of block modes is as shown below.
Forthisreason,infact,(*1)transitionstoCas,Auto,orMAN,whicheverissetpermittedin
MODE_BLK.Permittedandhasthelowestprioritylevel.
FA0105.EPS
Higher priority
level
Lower priority
level
ROut RCas Cas Auto Man
(*2)isonlywhenAutoissetaspermittedmodebyMODE_BLK.Permitted.
Note: Due to initialization of the cascade connection, if the upstream is a control block, the
transition to the Cas mode occurs in the following sequence:
RCas/ROut -> Auto -> Cas

Table of Contents

Other manuals for YOKOGAWA ADMAG TI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ADMAG TI Series and is the answer not in the manual?

YOKOGAWA ADMAG TI Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelADMAG TI Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals