<6. Parameter Lists>
216
IM 01E21A02-03EN
Relative
Index
Index
Parameter
Name
Default Value
Write
Mode
Description
DI1 DI2 DI3
21 6021 6121 6221 ACK_OPTION 0xFFFF AUTO
Sets operation
to acknowledge
(acknowledgmentfor
thealarm)ofvarious
alarms. By setting a bit
to the alarm, the device
operates for the alarm as if
it is acknowledged without
the acknowledgment.
Bit assignment complies
with the Communication
standardspecications.
22 6022 6122 6222 DISC_PRI 0 AUTO Speciesthealarmpriority.
23 6023 6123 6223 DISC_LIM 0 AUTO
Indicates the input
status for discrete alarm.
Meanwhile, to activate an
alarm on communication,
it is necessary to specify
the priority for alarm
activation in advance. To
activate an alarm, set 3
or more. By sending with
priority information being
added in a communication
frame when the alarm is
activated, for example, the
alarm is used to apply a
ltertoignorevaluesbelow
thespeciedpriorityonthe
host side.
24 6024 6124 6224 DISC_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0(State0)
AUTO
-
-
-
-
Indicates the status related
to discrete alarm.