<5. Functions>
54
IM 01E21A02-03EN
 Flow noise
Menu path
Display Devicesetup►Diag/Service►Diagnosis►Flownoise►Result►(seebelow)
F
OUNDATION
Fieldbus
ProcessVariables►DTB►ProcessVariables►DynamicVariables►DeviceVariables
►FlowNoiseValue►(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
DTB 20
- Flow Noise Value.Status Statusoftheownoisevalue
Value Flow Noise Value.Value Displaystheownoisevalue.
This parameter can be used only for AXG, not for AXW.
 Electrode adhesion detection
Menu path
Display Devicesetup►Diag/Service►Diagnosis►Adhesion►Result►(seebelow)
FOUNDATION
Fieldbus
ProcessVariables►DTB►ProcessVariables►DynamicVariables►DeviceVariables
►AdhesionValue►(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
DTB 14
- Adhesion Value.Status
Status of the resistance value
of the electrode
Value Adhesion Value.Value
Displays the resistance value of
the electrode.
 Electrode potential
Menu path
Display Devicesetup►Diag/Service►Diagnosis►Emptycheck►(seebelow)
F
OUNDATION
Fieldbus
ProcessVariables►DTB►ProcessVariables►DynamicVariables►DeviceVariables
►(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
DTB 16
-
ElectrodeAValue►Electrode
A Value.Status
Status of voltage value
between electrode A and
electrode C
Value
ElectrodeAValue►Electrode
A Value.Value
Displays the voltage value
between electrode A and
electrode C.
DTB 18
-
ElectrodeBValue►Electrode
B Value.Status
Status of voltage value
between electrode B and
electrode C
Value
ElectrodeBValue►Electrode
B Value.Value
Displays the voltage value
between electrode B and
electrode C.