<5. Functions>
60
IM 01E21A02-03EN
 Frequency output/pulse output
Menu path
Display Devicesetup►Detailedsetup►Pulse/Statusout►PO1/SO1►(seebelow)
F
OUNDATION
Fieldbus
DeviceConguration►MTB►DeviceConguration►Maintenance►Pulse/StatusOut
►(seebelow)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
MTB 107 Low cut Pulse 1 Low Cut
Speciesthelow-cutvalueof
the frequency output and pulse
output.
 Totalizer
Menu path
Display Devicesetup►Detailedsetup►Totalizer►(seebelow)
F
OUNDATION
Fieldbus
DeviceConguration►STB►DeviceConguration►Conguration►Totalizer►(see
below)
Block
Name
Relative
Index
Parameter
Description
Display F
OUNDATION Fieldbus
STB 67 Totalizer1►Lowcut Totalizer1►Total1Lowcut
Speciesthelow-cutvalueof
totalizer 1.
STB 76 Totalizer2►Lowcut Totalizer2►Total2Lowcut
Speciesthelow-cutvalueof
totalizer 2.
Anactualvaluewhichmakeslowcuttinge󰀨ectivehas±0.5%hysteresisfromthesetlow-
cutvalue.Thehysteresiswidthonthenegativeside(goingintothelowcutwhenowrateis
decreasing)andthepositiveside(goingoutoflowcutwhenowrateisincreasing)areas
follows:
(1)Negativeside
 =Low-cutsetpoint-(Minimumspansetwithmultirangex0.5%)
(2)Positiveside
 =Low-cutsetpoint+(Minimumspansetwithmultirangex0.5%)
Example:Whensettingtospanofvolumetricowrate=10.0m3/h,
Low-cutvalue=1.0m3/h
(1) Negativeside
 =1.0[m
3
/h]–(10.0[m
3
/h]x0.5[%])
 =0.95[m
3
/h]
(2) Positiveside
 =1.0[m
3
/h]+(10.0[m
3
/h]x0.5[%])
 =1.05[m
3
/h]