Configuration
Parameter manual b maXX BM5800
Document No.: 5.16029.03 Baumüller Nürnberg GmbH
184
of 814
3.4
time compensation is adapted according to the presently used switch frequency.
This can be different to the switch frequency at the moment of the measurement.
Better dead time compensation is reached if the used switch frequency and switch
frequency at the time of measurement are equal.
123.2 Status
This parameter shows the current status of the identification.
NOTE!
There is no way proving, if dead time measurement was executed by "Adaption ac-
cording to PWM frequency", successfully.
Value Meaning
0 Identification inactive or completed
1 Preparation for identification
2 Identification starting
3 Switch on voltage setting
4 Voltage setting
5 Starts identification of the resistance
6 Identification of resistance or inductance
7 Error during identification of resistance or inductance
8
Identification of dead time in progress
9
10
11
12
13 Error during identification of dead time
14 Identification ready
15 Identification switched off
16 Identification cannot be switched on
17 Identification error: Set Value voltage too great.
18 Identification error: Voltage limit accessed
19 Identification error: Timeout (60 seconds) while measuring the resistance
20 Identification interrupted