Description of the Software Modules and Parameters
Parameter manual b maXX BM5800
Document No.: 5.16029.03
447
of 814
3
3.7.2.6 Description of the Parameters
29.1 Command
Switching the filter on/off.
If the filter parameterization is active as a biquad filter, then the filter coefficients cannot
be calculated / changed individually, but are connected to the parameters
Z29.30– to
Z29.41–. Furthermore, the coefficients are automatically calculated again during a
change of the RT0 cycle time (Z1.8–).
29.2 Status
Display of filter status (on / off)
29.6 Input value
Displays the input to the filter.
29.7 Output value
Displays the output of the filter.
Bit Meaning
1 ... 0 0: Switch off filter
1: Filter as a current set value filter
(Active mains rectifier unit: Switch on filter)
2: Filter directly following the speed controller
2 Filter parameterization as a biquad filter
3 Recalculate filter (if bit 2 = 1)
7 ... 4 Switch on/switch off PT
1
filter 1 to 4
10 ... 8 Switch on/switch off biquad filter 1 to 3
13 ... 11 Switch on/switch off notch filter 1 to 3
Value Meaning
0 Filter is switched off
1 Filter is switched on