Diagnosis
Parameter manual b maXX BM5800
Document No.: 5.16029.03 Baumüller Nürnberg GmbH
696
of 814
3.10
3.10.3.2 Description of the Parameter
104.1 Command
This parameter can be used to switch the FFT analyzer function on or off.
104.2 Status
This parameter shows the current status of the module.
104.14 Frequency for sinus
generator
FLOAT 0 8000 0 Hz 1:1 X X
104.15 Signal out FLOAT -1e+9 1e+9 0 1:1 X X
104.16 Input signal 1 FLOAT -1e+9 1e+9 0.000000e+00 1:1 X X
104.17 Input signal 2 FLOAT -1e+9 1e+9 0.000000e+00 1:1 X X
104.18 Actual average DINT 0 20000 0 1:1 X X
104.19 Max. frequency FLOAT 0.000000e+00 8000 2000 Hz 1:1 X X
104.20 Frequency resolution FLOAT 0.000000e+00 62.5 9.765625e-01 Hz 1:1 X X
104.21 FFT data FLOAT 0 0 0 1:1 X X
104.22 Prbs register length UINT 0 19 19 1:1
104.23 Prbs register clock UINT 1 0xFFFF 1 1:1
FFT Command Meaning
0 Stop
1 Run
Status Meaning
0 Idle
1 Initialization Memory
3 Initialization Window Function
5 Start Average
8 Get Signal Initialization
9 Get Signal
11,12 Windowing Signal Ch1, Ch2
13,15 FFT Ch1, Ch2
17 Standardization
20,22 Auto, Cross Spectrum
24, 25, 26 ÜTF, PHI, Coherence Calculation