Monitoring
Parameter manual b maXX BM5800
Document No.: 5.16029.03 Baumüller Nürnberg GmbH
708
of 814
3.11
3.11.3 Overload monitoring of the power unit
Overload monitoring protects the power unit against thermal monitoring. Thereby thermal
load is emulated and monitored by a model. There are two methods for this:
m Temperature model (enabled, if complete thermal data set is available in the de-
vice's characteristics (Z175.2 bit 3 = 1) and if the temperature model is selected
(Z175.1 bit 1 = 1).
m Ixt model (is operated, if the temperature model is not enabled).
Parameter Status PU temperature model Z175.2 bit 0 displays, which method is en-
abled.
3.11.3.1 Ixt model
The thermal load of the complete device is emulated on the basis of total current and peak
current time.
Figure 182: Overload monitoring of the power unit (Ixt model)
Current controller Iq actual value fil-
tered
47.5
Current controller Id actual value fil-
tered
47.6
Total current actual value (I
ist
) [A
eff
]
LT nominal current 4 kHz / 8 kHz (I
nenn
) [A
eff
] 6.26
LT maximum current 4 kHz / 8 kHz (I
max
) [A
eff
] 6.25
Maximum current for the drive (I
grenz
) [A
eff
] 19.6
LT Overload time (t
u
) [s] 129.22
LT Heat sink temperature actual value (
ist
) [°C] 130.1
LT Ixt value (Ixt) [%] 6.27
LT Overload factor max (u
max
) [%]
LT Overload factor current (u) [%]
6.27
PT1

130.1
5000_1004_rev02_int.cdr
x+y
2
2
Display
It value [%]
Limitation on
Warning 206
LT monitoring
activated
Current controller
Iq actual value filtered
47.5
Current controller
Id actual value filtered
47.6
Power unit
nominal current
(6.26)
Ixt
offset
temperature actual value
actual
I
actual
Power
unit
1
47.5
2
47.6
2
+