Description of the Software Modules and Parameters
Parameter manual b maXX BM5800
Document No.: 5.16029.03
293
of 814
3
3.5.1.4 State Transitions in the Device Controller of the axis units
0 Input to the State Machine NOT READY TO SWITCH ON
n Event:
m Switch on supply to electronics
m Hardware reset or
m Software reset
n Action:
m Start initialization and self test
1 NOT READY TO SWITCH ON SWITCH-ON INHIBIT
n Event:
m Initialization and self test completed without error
n Action:
m None
2 SWITCH-ON INHIBIT READY TO SWITCH ON
n Event:
– Drive activation by control word:
m "Shut-down" command
n Condition:
m axis not parked
n Action:
m None
3 READY TO SWITCH ON SWITCHED ON
n Event:
– Drive activation by control word:
m "Switch On" command
n Condition:
m Power supply reports operational readiness / main supply voltage applied and
n Action:
m None
4 SWITCHED ON OPERATION ENABLED
n Event:
– Drive activation by control word:
m "Enable Operation" command
n Action:
m Drive function is enabled and
m Holding brake is enabled
(only if brake is in Automatic mode (Parameter Z134.1– Bit 0 = 1)