Set Value Generators
Parameter manual b maXX BM5800
Document No.: 5.16029.03 Baumüller Nürnberg GmbH
354
of 814
3.6
n change of set value from effective set value at ramp function generator output
Z110.3 to 0%. This causes a constant braking time from all speeds at ramp func-
tion generator output.
m The set SS1 stop time Z110.21 applies to
n change of set value from effective speed to 0%. This causes a constant braking time
from all speeds.
n change of set value from 100% to 0% (braking deceleration independent of the in-
stantaneous speed).
More functions:
m Input value limited by Z110.15 and Z110.16.
m Monitoring of the hardware limit switch. The behavior at an active hardware limit switch
can be chosen via
Z110.2 bit 8 and 9. The limit switch monitoring is switched on via
Z121.1 bit 1 = 1.
m Additional additive input Z110.17 with format of the 32 bit input Z110.4.
m Transparency mode: Switch off ramp generator (output = input)
m Optional interpolation of the ramp function generator set value input (see chapter Z
3.6.1.1 on Zpage 358)
For correct functioning of the braking procedures on the Quick Stop or Ramp-down
ramps, the speed controller must be adequately configured.
Trapezoidal Pro-
file
The ramp-up and ramp-down times refer to a change in the input set value of +100% or
-100%.
The resulting times for other set value changes are calculated as follows:
T
ResRamp-up
= T
Ramp-up
* Set value change / 100 %
T
ResRamp-down
= T
Ramp-down
* Set value change / 100 %