Set Value Generators
Parameter manual b maXX BM5800
Document No.: 5.16029.03 Baumüller Nürnberg GmbH
368
of 814
3.6
110.3 Output
Output value of the ramp function generator.
Standardization:
100% = Maximum drive speed (Z110.13–, [rpm])
The output value of the ramp function generator is written to the input of the set value
manager (chapter
Z 3.5.5–). For this purpose the value must be converted from the 100%
standardization to 32-bit increments/revolution per sensing.
The permitted range of the set value manager input is ± (2
31
-1) increments per sensing.
If the converted ramp function generator exceeds this range it is limited and the error 910
"Overspeed detected at the set value input".
At the standard sensing time of the ramp function generator of 1 ms the permitted set val-
ue range ± 29999 rpm. If the ramp function generator is operating in the fieldbus task
(
Z110.2– Mode bit 16 = 1), its cycle time is set by means of the Z131.18– Fieldbus cycle
time and the Z131.20– Division ratio fieldbus task.
Example:
Z110.22– Active cycle time ramp generator = 500 µs Set value range ± 59999 rpm
Z110.22– Active cycle time ramp generator = 2000 µs Set value range ± 14999 rpm
110.4 Input 32-bit
Ramp generator input value with 32-bit resolution. This input is activated instead of the
16-bit input by means of
Z110.2– Ramp function generator mode bit 5 = 0.
Standardization:
100% = Maximum drive speed (Z110.13–, [rpm])
110.5 Input 16-bit
Ramp generator input value with 16-bit resolution. This input is activated instead of the
32-bit input by means of
Z110.2– Ramp function generator mode Bit 5 = 1.
Standardization:
100% = Maximum drive speed (Z110.13–, [rpm])
110.6 Ramp-up time
Acceleration ramp for the speed-controlled operating modes.
The time selected here applies to a 100% set value change