110.7 Ramp-down time
Deceleration ramp for the speed-controlled operating modes.
The time selected here applies to a 100% set value change
110.8 Quick stop time
The Quick stop ramp operates during all Quick stop procedures, not only in the speed-
controlled operating modes.
Depending on bit 7 of the parameter Z110.2 Mode the quick stop time applies to
m change of set value from 100% to 0% Z110.2 bit 7 = 0,
m change of set value from actual set value at ramp function generator output Z110.3
to 0%. This causes a constant braking time from all speeds at ramp function generator
output.
For correct functioning of the braking procedures on the Quick stop or Ramp-down
ramps, the speed controller must be adequately configured.
110.9 S-Curve ramp-up time
Rounding of the ramp corners on ramp-up for the speed-controlled operating modes. The
time selected here applies to a 100% set value change.
The set S-Curve ramp-up time must be less than the set ramp-up time.
Total ramp-down time for a 100% set value change:
T
TotalRamp-upTime
= T
Ramp-upTime
+ T
SCRamp-upTime
110.10 S-Curve ramp-down time
Rounding of the ramp corners on ramp-down for the speed-controlled operating modes.
The time selected here applies to a 100% set value change
The set S-Curve ramp-down time must be less than the set ramp-down time.
Total ramp-down time for a 100% set value change:
T
TotalRamp-downTime
= T
Ramp-downTime
+ T
SCRamp-downTime