EasyManua.ls Logo

Baumuller b maXX BM5800 - Page 249

Baumuller b maXX BM5800
816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of the Software Modules and Parameters
Parameter manual b maXX BM5800
Document No.: 5.16029.03
249
of 814
3
150.28 Output lower limit PID controller 2
Lower limit of the PID controller output.
If the output is limited with this limit, it will be signalized in Z150.18 bit 4.
150.29 Set value PID controller 2
Value of the set value of the PID controller.
The source of this set value can be selected in Z150.20 „Source number set value PID
controller 2“.
If the source is not selected (Z150.20 = 0) the set value can be written via fieldbus or
an analogous input.
If the source is selected (Z150.20 0) and the value of the source parameter is less
than the minimum value or greater than the maximum value of the set value, the set value
is limited to its minimum or maximum value. This will be signalized in
Z150.18 bit 9.
150.30 Actual value PID controller 2
Value of the actual value of the PID controller.
The source of this actual value can be selected in Z150.21 „Axis index PID controller 2“.
If the source is not selected (Z150.21 = 0) the actual value can be written via fieldbus
or an analogous input.
If the source is selected (Z150.21 0) and the value of the source parameter is less
than the minimum value or greater than the maximum value of the actual value, the actual
value is limited to its minimum or maximum value. This will be signalized in
Z150.18
bit 9.
150.31 Output PID controller 2
Value of the output of the PID controller.
The target of the output can be selected in Z150.22 „Target number output PID control-
ler 2“.
The output is set to 0 at deactivated PID controller.
NOTE!
If the lower limit is less than the minimum value of the linked target parameter, then
the output is limited at writing on the target parameter to the minimum value of the
linked target parameter if necessary. This will be signalized in
Z150.18 bit 8.

Table of Contents

Related product manuals