Error messages and troubleshooting
Parameter manual b maXX BM5800
Document No.: 5.16029.03
729
of 814
4
Blockage monitor-
ing
This monitoring function checks the motor speed and the motor current.
If the "Blockage monitoring interval" time frame meets the following two conditions, then
the error message/warning "Drive blocked" is signaled by the controller and a pulse inhibit
takes place immediately.
m Motor speed = 0
m The motor current output by the device is the same as the set motor limiting current
(current limit).