- 104 -
Function
Code
Parameter Name Setting Range Default Unit
Property
FE-13
Elevator function
selection 1
0–65535
If the bit is set to 1, the
function expressed is
enabled.
Bit0: Reserved
Bit1: Reserved
Bit2: Re-leveling function
Bit3: Door pre-open function
Bit4: Reserved
Bit5: Forced door close
Bit6: Door open valid at non-
door zone in the inspection
state
Bit7: Door open and close
once after inspection turned
to normal
Bit8: Reserved
Bit9: Independent running
Bit10: Reserved
Bit11: Door re-open after car
call of the present oor
Bit12–Bit15: Reserved
0 -
☆
FE-14
Elevator function
selection 2
0–65535
If the bit is set to 1, the
function expressed is
enabled.
Bit0: Reserved
Bit1: Door open holding at
open limit
Bit2: Door close command
not output upon door close
limit
Bit3: Manual door
Bit4: Auto reset for RUN and
brake contactor stuck
Bit5: Slow-down switch stuck
detection
Bit6–Bit9: Reserved
Bit10: NO/NC output selection
of shorting PMSM stator
contactor
Bit11: Reserved
Bit12: Fan/Lamp output
Bit13–Bit15: Reserved
0 -
☆