User Manual Troubleshooting
- 187 -
Fault
Code
Name Possible Causes Solution Level
Err45
Slow-down
switch position
abnormal
101: The down slow-down
distance is insufcient
during shaft auto-tuning.
102: The up slow-down
distance is insufcient
during shaft auto-tuning.
103: The slow-down
position is abnormal during
normal running.
104, 105: The elevator
speed exceeds the
maximum speed when
slow-down is enabled.
101 to 103:
Check whether the up slow-
down and the down slow-down
are in good contact.
Check the signal feature (NO,
NC) of the up slow-down and
the down slow-down.
104, 105:
Ensure that the obtained slow-
down distance satises the slow-
down requirement at the elevator
speed.
4B
Err46
Re-leveling
abnormal
101: The leveling signal is
inactive during re-leveling.
102: The re-leveling running
speed exceeds 0.1 m/s.
103: At startup of normal-
speed running, the re-
leveling state is valid and
there is shorting door lock
circuit feedback.
104: During re-leveling, no
shorting door lock circuit
feedback or door lock signal
is received 2s after shorting
door lock circuit output.
101: Check whether the leveling
signal is normal.
102: Check whether the encoder
is used properly.
103, 104:
Check whether the signal of
the leveling sensor is normal.
Check the signal feature (NO,
NC) of the feedback contact on
the shorting door lock circuit
contactor, and check the relay
and wiring of the SCB-A board.
2B
Err47
Shorting door
lock circuit
contactor
abnormal
101: During re-leveling
or pre-open running, the
shorting door lock circuit
contactor outputs for
continuous 2s, but the
feedback is invalid and the
door lock is disconnected.
102: During re-leveling
or pre-open running, the
shorting door lock circuit
contactor has no output,
but the feedback is valid for
continuous 2s.
103: During re-leveling
or pre-open running, the
output time of the shorting
door lock circuit contactor is
larger than 15s.
101, 102:
Check the signal feature (NO,
NC) of the feedback contact on
the shorting door lock circuit
contactor.
Check whether the shorting
door lock circuit contactor acts
properly.
103:
Check whether the leveling
and re-leveling signals are
normal.
Check whether the re-leveling
speed is set too low.
2B