- 91 -
Function
Code
Parameter Name Setting Range Default Unit
Property
F6-72
Emergency evacuation
switching speed
0.010–0.630 0.010 m/s
★
F6-73
Evacuation parking
oor
0 to F6-00 0 -
★
F6-74 Blinking advance time 0.0–15.0 1 s
☆
F6-75
Waiting time for
switchover from
shorting stator braking
mode to controller
drive
0.0–45.0 20.0 s
☆
Group F7: Output Terminal Parameters
F7-00 Y0 function selection
Y0 designated for function
32 "emergency evacuation at
power failure"
Range: 00–05 or 32
00: Invalid
01: RUN contactor output
02: Brake contactor control
03: Higher-voltage startup of
brake
04: Lamp/Fan running
05: Shorting PMSM stator
contactor
00 -
★
F7-01 Y1 function selection 01 -
★
F7-02 Y2 function selection 02 -
★
F7-03 Y3 function selection 04 -
★
F7-04 Y4 function selection
06–99
00: Invalid
06: Door 1 open output
07: Door 1 close output
08: Door 2 open output
09: Door 2 close output
10: Low 7-segment a display
output
11: Low 7-segment b display
output
12: Low 7-segment c display
output
13: Low 7-segment d display
output
(To be continued)
00 -
★
F7-05 Y5 function selection 00 -
★
F7-06 Y6 function selection 06 -
★
F7-07 Y7 function selection 07 -
★
F7-08 Y8 function selection 08 -
★