5-37
5-4 Analog Signal
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
5
Functions
5-4 Analog Signal
The following explains the Inverter's analog input/output signals.
Analog Input (FV, FI)
The Inverter has 2 types of external analog input terminals.
FV-SC terminal: 0 to 10 V
Variable Resistor (volumes) inputs are also recognized as voltage inputs in the context of
Inverter signals.
FI-SC terminal: 0 to 20 mA
If the current is 4 to 20 mA, set A103 to 20%.
The following functions can be allocated to analog input signals. The required settings are as
follows.
Parameter
No.
Setting item Function name Data
Default
setting
Unit
A001
Frequency
Reference
*1
Frequency
Reference Selection
1
01: Digital Operator
(volume) 02 −
A071
PID Feedback
Selection
*2
PID Selection
01: Enabled
02: Reverse output
enabled
00 −
A076
PID Feedback
Selection
00: Current (FI)
01: Voltage (FV)
00 −
A071
PID Feedforward
Selection
*3
PID Selection
01: Enabled
02: Reverse output
enabled
00 −
A079
PID Feedforward
Selection
01: FV (vortage)
02: FI (current)
00 −
b040
Torque Limit
Selection
*4
Torque Limit
Selection
02: Analog voltage input
00 −
P033
Torque Control
Torque Reference
Input Selection
00: Terminal FV
10 V = 200%
00 −
01: Terminal FI
20 mA = 200%
C001 to
C007
Multi-function Input
Selection
52: ATR
(Torque reference input
permission)
−−
*1.Switch among the volume, current and voltage using FV/FI Selection (A005). Volume (VR) on the
external Digital Operator 3G3AX-OP01.
*2.If Frequency Reference is set to Control circuit terminal block (A001 = 01) and PID Selection (A071) is
enabled, PID is given priority and the analog input specified by A076 is allocated for PID feedback.
Regardless of A005 or the FV/FI terminal status, the analog input not selected by A076 is allocated to
Frequency Reference.
*3.Even when the specified analog input is overlapping with the target value or feedback value, the setting
of A079 is applied as is.
*4.Only the analog voltage 10 V = 200% of the torque limit value. The FV/FI terminal is not allocated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE MX2 SERIES and is the answer not in the manual?

Omron SYSDRIVE MX2 SERIES Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE MX2 SERIES
CategoryInverter
LanguageEnglish

Related product manuals