7-9
7-2 Troubleshooting
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
   7
Maintenance Operations
7-2 Troubleshooting
If the Inverter malfunctions or does not function as expected although no error display is
shown, take a remedial action by referring to the information below.
If the Inverter trips after showing an error display, refer to "Error Display and Remedial Actions"
on page 7-1.
Condition Possible cause Remedial actions
R
eference
Page
The power does 
not turn on. (The 
main POWER LED 
indicator is not lit).
The shorting bar between 
terminals +1 and P/+2 or 
DC reactor is disconnected.
Connect the shorting bar or DC reactor.
2-6
to
2-14 
The input wire is disconnected.
Check the wiring.
The motor does not 
turn after a RUN 
command is 
issued.
The setting of RUN 
Command Selection 
(A002) is not correct.
Set the correct RUN Command Selection 
(A002). 5-22
The setting of Frequency 
Reference Selection 
(A001) is not correct.
Set Frequency Reference Selection 
(A001) correctly according to the 
frequency reference input method, and 
specify the frequency.
5-15
The frequency is set to 0 
Hz.
If Frequency Reference Selection (A001) is set to 
"01: Control circuit terminal block, "input to the FV 
or FI terminal an analog voltage or current signal 
corresponding to the frequency. Refer to 
"Frequency Reference Selection and Output 
Frequency Setting" on page 5-15 for details on 
analog voltage/current switching.
If Frequency Reference Selection (A001) 
is set to "02: Digital Operator", set the 
frequency in Output Frequency Setting 
(F001).
Enter the frequency according to the set 
value in Frequency Reference Selection 
(A001). (The entered frequency is 
displayed under F001).
In the case of multi-step speed operation, 
set the frequency in Multi-step Speed 
Reference 0 to 15 (A020 to A035, A220).
5-63
No multi-function input 
terminal (RUN command) 
is allocated.
If a multi-function input terminal is used to 
issue a RUN command, allocate "00: FW" or 
"01: RV" to the applicable terminal.
If a RUN command is issued using the 3-wire 
input method, allocate "20: STA", "21: STP, 
"or "22: F/R". 
5-29
One of multi-step speed 
settings "02: CF1" to "05: 
CF4" is allocated to a 
multi-function input 
terminal and the terminal 
is turned ON.
Turn OFF the multi-step speed setting. (If 
the multi-step speed setting is turned ON, 
multi-step speed operation becomes 
effective. Accordingly, operation is not 
performed if the applicable frequency set in 
Multi-step Speed Reference 1 to 15 (A021 
to A035) is 0 (default value)).
5-63
Both the forward input 
and reverse input 
terminals are turned ON.
To use the forward or reverse input 
terminal to issue a RUN command, turn 
only one of the two terminals ON.
5-23