5-9 Functions Relating to Protections, Warnings and Various Output Signals
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
5
Functions
Window Comparator ( WCFV/WCFI) (Disconnection Detection FVdc/FIdc)
The Inverter activates the window comparator output when the FV/FI analog input value is
within the upper and lower limit levels of the window comparator. Analog inputs such as
disconnection detection can be monitored on a desired level.
Hysteresis widths can be set for the window comparator upper and lower limit levels.
Levels and hysteresis widths can be set separately for individual FV/FI inputs.
The analog value to be adopted upon WCFV/WCFI output can be fixed to a desired value. Set
values in FV/FI Disconnection Operation Levels (b070/b071). If "no" is set, the analog input
value will be directly reflected.
FVdc/FIdc outputs are the same as WCFV/WCFI, respectively.
Note: The window comparator upper/lower level settings have nothing to do with the external frequency
start/end settings.
Set the voltage limits as percentages [%] corresponding to 0 to 10 V, and current limits as
percentages [%] corresponding to 0 to 20 mA.
Parameter
No.
Function name Data range
Default
setting
Unit
b060
Window Comparator
FV Upper Limit Level
Lower limit level + Hysteresis width ×
2 (0 min.) to 100.
Set an upper limit level.
100. %
b063
Window Comparator
FI Upper Limit Level
b061
Window Comparator
FV Lower Limit Level
0 to Upper limit level - Hysteresis
width × 2 (100 max.)
Set an upper limit level.
0. %
b064
Window Comparator
FI Lower Limit Level
b062
Window Comparator
FV Hysteresis Width
0 to (Upper limit level - Lower limit
level) / 2 (10 max.)
Set a hysteresis width for the upper
and lower limit levels.
0. %
b065
Window Comparator
FI Hysteresis Width
b070
Analog Operation
Level at FV
Disconnection
0. to 100./no (ignored)
Set the analog value to be adopted
upon WCFV/WCFI (FVdc/FIdc)
output.
no −
b071
Analog Operation
Level at FI
Disconnection
C021 to C022
C026
Multi-function Output
Terminal Selection
Multi-function Relay
Output Function
Selection
27: FVdc (Analog FV disconnection
detection)
−−
28: FIdc (Analog FI disconnection
detection)
54: WCFV (Window comparator FV)
55: WCFI (Window comparator FI)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE MX2 SERIES and is the answer not in the manual?

Omron SYSDRIVE MX2 SERIES Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE MX2 SERIES
CategoryInverter
LanguageEnglish

Related product manuals