6-16
6-5 Explanation of Each Parameter No.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
6
Communication Function
Writing Into Multiple Holding Register [10h]
Writes into consecutive multiple registers.
Example) Set Acceleration Time Setting 1 (F002) to "10 s" for the Inverter whose slave
address is "1".
Since holding registers "1103h and 1104h" used for Acceleration Time Setting 1 (F002) have a
data resolution of 0.01 s, the data to be written should be "1000 (0000 03E8h)" when setting 10 s.
(Register address) = (Register number)
1
0000 03E8h 1000d 10.00 s
Query:
Response:
*1. There is no response for broadcasting.
*2. Note that the holding register start address is "1102h", which is smaller by 1 than the register number
"1103h". The register number less 1 corresponds to the register address.
*3. Specifies the number of actual bytes to change to, not the number of holding registers.
Refer to "Exceptional Response" on page 6-18 if the writing into the multiple registers cannot
be performed normally.
No. Field name
Example
(Hex)
1 Slave address
*1
01
2 Parameter No. 10
3 Register start address (MSB)
*2
11
4 Register start address (LSB)
*2
02
5 Number of registers (MSB) 00
6 Number of registers (LSB) 02
7 Number of bytes
*3
04
8 Written data 1 (MSB) 00
9 Written data 1 (LSB) 00
10 Written data 2 (MSB) 03
11 Written data 2 (LSB) E8
12 CRC-16 (MSB) B2
13 CRC-16 (LSB) 98
No. Field name
Example
(Hex)
1 Slave address
*1
01
2 Parameter No. 10
3 Register start address (MSB)
*2
11
4 Register start address (LSB)
*2
02
5 Number of registers (MSB) 00
6 Number of registers (LSB) 02
7 CRC-16 (MSB) E5
8 CRC-16 (LSB) 34