5-10
5-1 Monitor Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
5
Functions
User Selection Monitor (2 Types) [d050]
Desired two monitor items can be set and monitored by switching the item using the Increment/
Decrement keys.
Set the parameter numbers to be monitored in b160 and b161.
Example) To monitor d001, set "001" in b160/b161.
When d001/d007 Frequency Setting Mode Selection (b163) is set to "01: Enabled," the output
frequencies in d001 and d007 can be changed using the Increment/Decrement keys during
operation. It cannot be changed if d001 and d007 are monitored using d050.
Inverter Mode Monitor [d060]
Displays the current Inverter mode.
The Inverter mode is changed using b171. For details, refer to "Inverter Mode Selection" on
page 5-175.
Parameter
No.
Function name Data
Default
setting
Unit
d050
User Selection Monitor
(2 Types)
The two items set in b160 and b161
are monitored.
b160 d050 Monitor Target 1
001 to 030
Corresponding to d001 to d030.
*1
001
b161 d050 Monitor Target 2 002
*1.Fault Monitor parameters (d081 to d086) are excluded.
Data of monitor
target 1 set in b160
Data of monitor
target 2 set in b161
dk0k5k0
5k0.0k0
1k2.3
Parameter
No.
Function name Data
Default
setting
Unit
d060
Inverter Mode
Monitor
I-C
IM (induction motor) heavy load mode
−−
I-V
IM (induction motor) light load mode
H-I
IM (induction motor) high-frequency
mode