With multi-step speed binary operation, the wait time until the terminal input is determined can
be set using Multi-step Speed/Position Determination Time (C169) (set value × 10 ms =
Determination time). This prevents the transition status before input establishment from being
applied.
If no input is made during the time set in C169, the data is determined.
Note that the longer the determination time, the slower the input response.
Bit Operation
Selection of multi-step speed references 0 to 7 becomes possible when SF1 to SF7 (32 to 38)
are allocated to Multi-function Input Selections (C001 to C007).
Use Multi-step Speed References 1 to 7 (A021 to A027) to set the frequencies for SF1 to SF7.
Multi-step speed operation is given priority over Frequency Reference Selection (A001). However,
the frequency reference 0 conforms to the setting of Frequency Reference Selection (A001).
When several terminals are simultaneously turned on, priority is given to the terminal with the
smallest number.
The × mark in the above table means that speed is selected regardless of ON/OFF status.
Multi-step speed SF7 SF6 SF5 SF4 SF3 SF2 SF1
Speed reference 0 OFF OFF OFF OFF OFF OFF OFF
Speed reference 1 ××××××ON
Speed reference 2 ×××××ON OFF
Speed reference 3 ××××ON OFF OFF
Speed reference 4 ×××ON OFF OFF OFF
Speed reference 5 ××ON OFF OFF OFF OFF
Speed reference 6 × ON OFF OFF OFF OFF OFF
Speed reference 7 ON OFF OFF OFF OFF OFF OFF
Determination Time
(C169) Zero
Frequency reference
CF1 input
Determination
Time (C169)
Determination Time
(C169) available
CF2 input
CF3 input
CF4 input
1
9
11
15
13
5
4
SF1
SF2
SF3
SF4
SF5
SF6
SF7
FW
Speed reference 1
Speed reference 2
Speed reference 3
Speed reference 4
Speed reference 5
Speed reference 6
Speed reference 7
Speed reference 0
Speed reference 1
The frequency at speed
reference 0 conforms to
the setting of A001.