5-124
5-9 Functions Relating to Protections, Warnings and Various Output Signals
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
   5
Functions
RUN Time/Power ON Time Over (RNT/ONT)
The RUN time/power ON time over (RNT/ONT) signal is output when the total sum of the
Inverter power ON time and RUN time exceeds the time set in Power ON Time Level (b034).
RUN Time Over (RNT)
Allocate "11: RNT (RUN time over)" to any Multi-function Output Terminal Selections (C021 to
C022) or Multi-function Relay Output Function Selection (C026).
Set Power ON Time Level (b034). 
Power ON Time Over (ONT)
Allocate "12: ONT (Power ON time over)" to any Multi-function Output Terminal Selections
(C021 to C022) or Multi-function Relay Output Function Selection (C026).
Set Power ON Time Level (b034). 
Parameter 
No.
Function name Data
Default 
setting
Unit
b034
RUN Time/Power 
ON Time Level
0.
Function disabled 
0. −
1. to 9999.
Set in increments of 10 hours (10 to 99,990 
hours).
1000 to 6553
Set in increments of 100 hours (100,000 to 
655,350 hours).
C021 to C022
C026
Multi-function 
Output Terminal 
Selection
Multi-function 
Relay Output 
Function Selection 
11: RNT (RUN time over)
−−
12: ONT (Power ON time over)
Related functions d016, d017