5-124
5-9 Functions Relating to Protections, Warnings and Various Output Signals
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
5
Functions
RUN Time/Power ON Time Over (RNT/ONT)
The RUN time/power ON time over (RNT/ONT) signal is output when the total sum of the
Inverter power ON time and RUN time exceeds the time set in Power ON Time Level (b034).
RUN Time Over (RNT)
Allocate "11: RNT (RUN time over)" to any Multi-function Output Terminal Selections (C021 to
C022) or Multi-function Relay Output Function Selection (C026).
Set Power ON Time Level (b034).
Power ON Time Over (ONT)
Allocate "12: ONT (Power ON time over)" to any Multi-function Output Terminal Selections
(C021 to C022) or Multi-function Relay Output Function Selection (C026).
Set Power ON Time Level (b034).
Parameter
No.
Function name Data
Default
setting
Unit
b034
RUN Time/Power
ON Time Level
0.
Function disabled
0. −
1. to 9999.
Set in increments of 10 hours (10 to 99,990
hours).
1000 to 6553
Set in increments of 100 hours (100,000 to
655,350 hours).
C021 to C022
C026
Multi-function
Output Terminal
Selection
Multi-function
Relay Output
Function Selection
11: RNT (RUN time over)
−−
12: ONT (Power ON time over)
Related functions d016, d017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE MX2 SERIES and is the answer not in the manual?

Omron SYSDRIVE MX2 SERIES Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE MX2 SERIES
CategoryInverter
LanguageEnglish

Related product manuals