5-58
5-6 Operation Functions
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
5
Functions
Reduced Voltage Startup Selection
Slowly increases voltage during motor startup.
Increase the value of b036 if you want to prevent a current surge at the start or when an
overcurrent trip occurs at the start. A smaller value increases the starting torque. As a result,
an overcurrent trip occurs more easily.
Parameter
No.
Function name Data
Default
setting
Unit
b036
Reduced Voltage
Startup Selection
0: Reduced voltage startup disabled
2 −
01: (Short) to 255 (Long)
Related functions b082
RUN command
(FW input)
Output
frequency
Output
voltage
Starting frequency
b082
b036 = 00
Reduced voltage startup disabled
RUN command
(FW input)
Output
frequency
Output
voltage
Starting frequency
b082
b036
Small Large
Reduced voltage startup enabled