5-128
5-9 Functions Relating to Protections, Warnings and Various Output Signals
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
   5
Functions
Communication Disconnection Detection Signal (NDc)
Enabled only when Modbus communication (Modbus-RTU) is selected for RS485
communication.
If a reception timeout error occurs, this signal is output until reception of the next data.
Set a time before reception timeout in Communication Error Timeout Time(C077).
For details, refer to Chapter 6, "Communication Function". 
Starting Contact Signal (FR)
While the Inverter is receiving the RUN command, a starting contact signal is output.
This signal is output regardless of the setting of RUN Command Selection (A002).
If inputs FW and RV are simultaneously turned on, the Inverter stops.
External controller
Inverter
Monitor timer
Communication error (NDc) output
Communication Error Timeout
(C077)
Parameter 
No.
Function name Data
Default 
setting
Unit
C077
Communications 
Error Timeout 
Time
0.00 to 99.99
Set a time before reception timeout. 0.00 s
C021 to C022
Multi-function 
Output Terminal 
Selection
32: NDc (Communication 
disconnection detection)
−−
C026
Multi-function 
Relay Output 
Function Selection 
Parameter 
No.
Function name Data
Default 
setting
Unit
C021 to C022
Multi-function 
Output Terminal 
Selection
41: FR (Starting contact signal) −−
C026
Multi-function 
Relay Output 
Function Selection 
Forward command (FW)
Reverse command (RV)
Starting contact (FR) output