9.4.1.1 Calculation of the BRM cooling time
BRM04/01 (230V_3AC)
100
1000
10000
0 0,5 1 1,5 2 2,5 3
3,5 4
Braking time [s]
PBdyn [W]
F = Factor
Cooling time = F * braking time
Example 1: For a braking time of 1s, a braking power of 1kW is required. The
Diagram shows the following:
The required values can be found in the range between characteristic F = 0.5 and
F = 1. In order to achieve operating safety, please select the higher factor, this
means that the required cooling time is 1s.
F * Braking time = cooling time
1 * 1s = 1s
Example 2: For a braking time of 0.5s, a braking power of 3kW is required. The
Diagram shows the following:
The required values can be found in the range between characteristic F = 2 and F
= 5. In order to achieve operating safety, please select the higher factor, this
means that the required cooling time is 2.5s.
F * Braking time = cooling time
5 * 0.5s = 2.5s
F=10
F=20
F=5
F=2
F=1
F=0.5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Compax3 I10T10 and is the answer not in the manual?

Parker Compax3 I10T10 Specifications

General IconGeneral
Rated Current10 A
Protection ClassIP20
Supply Voltage200-480 VAC
Control InterfaceEtherCAT, CANopen
Feedback OptionsResolver

Related product manuals