1.7.2. Conditions of utilization for UL certification Compax3S
UL certification for Compax3S
conform to UL:

according to UL508C
Certified

E-File_No.: E235342
The UL certification is documented by a "UL" logo on the
device (type specification plate).
ā€œULā€ logo:
Conditions of utilization
 The devices are only to be installed in a degree of contamination 2 environment
(maximum).
 The devices must be appropriately protected (e.g. by a switching cabinet).
 The X2 terminals are not suitable for field wiring.
 Tightening torque of the field wiring terminals ( green Phoenix plugs)

C3S0xxV2
0.57 - 0.79Nm 5 - 7Lb.in

C3S1xxV2,
C3S0xxV4, C3S150V4
0.57 - 0.79Nm 5 - 7Lb.in

C3S300V4
1.25 - 1.7Nm 11 - 15Lb.in
 Temperature rating of field installed conductors shall be at least 60°C Use copper
lines only
Please use the cables described in the accessories chapter (see on page 165,
see on page 166), they feature a temperature rating of at least 60°C.
 Maximum Surrounding Air Temperature: 45°C.
 Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes and 480 volts maximum.
ATTENTION
Danger of electric shock.
Discharge time of the bus condenser is 10 minutes.
 The drive provides internal motor overload protection.
This must be set so that 200% of the motor nominal current are not exceeded.
 Cable cross-sections
 Mains input: corresponding to the recommended fuses.
 Motor cable: corresponding to the Nominal output currents (see on page 213,
see on page 214)
 Maximum cross-section limited by the terminals mm
2
/ AWG

C3S0xxV2
2.5mm
2
AWG 12

C3S1xxV2,
C3S0xxV4, C3S150V4
4.0mm
2
AWG 10

C3S300V4
6.0mm
2
AWG 7
 Circuit breaker
In addition to the main circuit breaker, the devices must be equipped with a S271
K or S273 K circuit breaker with K characteristic made by ABB.
 C3S025V2: ABB, nom 480V 10A, 6kA
 C3S063V2: ABB, nom 480V, 16A, 6kA
 C3S100V2: ABB, nom 480V, 16A, 6kA
 C3S150V2: ABB, nom 480V, 20A, 6kA
 C3S015V4: ABB, nom 480V, 6A, 6kA
 C3S038V4: ABB, nom 480V, 10A, 6kA
 C3S075V4: ABB, nom 480V, 16A, 6kA
 C3S150V4: ABB, nom 480V, 20A, 6kA
 C3S300V4: ABB, nom 480V, 25A, 6kA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Compax3 I10T10 and is the answer not in the manual?

Parker Compax3 I10T10 Specifications

General IconGeneral
Rated Current10 A
Protection ClassIP20
Supply Voltage200-480 VAC
Control InterfaceEtherCAT, CANopen
Feedback OptionsResolver

Related product manuals