Parker EME
Compax3 device description
192-120100 N16 C3I10T10 - December 2010
PSUP30D6 Mains connection
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
3AC 230V 3AC 400V 3AC 480V
50Arms 50Arms 42Arms
325VDC ±10% 565VDC ±10% 680VDC ±10%
17kW 30kW 30kW
34kW 60kW 60kW
140W 140W 140W
device (=short circuit rating)
2 circuit breakers in line are
required
Cable protection measure:
MCB (K characteristic) with a rating of 63A / 4xxVAC
(depending on the input voltage)
Recommendation: (ABB) S203U-K63 (440VAC)
Device protection measure:
Circuit breakers 125A / 700VAC per supply leg in
accordance with UL category JFHR2
Requirement: Bussmann 170M1368 or 170M1568D
Only three-phase operation of the PSUP devices is permitted!
The PSUP30 mains module may only be operated with mains filter (see on
page 180)
Required mains filter for the PSUP30: 0.45 mH / 55 A
We offer the following mains filters:
ļµ LCG-0055-0.45 mH (WxDxH: 180 mm x 140 mm x 157 mm; 10 kg)
ļµ LCG-0055-0.45 mH-UL (with UL approval) (WxDxH: 180 mm x 170 mm x
157 mm; 15 kg)
Dimensional drawing: LCG-0055-0.45 mH