EasyManua.ls Logo

Radwin 2000+ SERIES - General; Internal ESD Protection Circuits; Protection against Lightning

Radwin 2000+ SERIES
276 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RADWIN2000+SeriesUserManual Release4.2.40 42
ProtectionAgainstLightning
ThegroundlugonanIDUH/HPshouldbeconnectedtotheprotectivegroundatall
times,byawirewithadiameterof18AWGorwider.Rackmountedequipmentshould
bemountedonlyingroundedracksandcabinets.
Further,youshould‐
Alwaysmakethegroundconnectionfirstanddisconnectitlast
Neverconnecttelecommunicationcablestoungroundedequipment
Ensurethatallothercablesaredisconnectedbeforedisconnectingtheground
4.2.3ProtectionAgainstLightning
Theuseoflightningprotectionisdependentonregulatoryandenduserrequirements.Allof
RADWINoutdoorunitsaredesignedwithsurgelimitingcircuitstominimizethe riskof
damageduetolightningstrike s.ForCAT5Ecables,RADWINrecommendstheuseoftheLPU
(LightningProtectionUnit).ForRFcables,RADWINrecommendstheuseofadditionalsurge
arrestordevicestoprotecttheequipmentfromnearbylightningstrik es.
4.2.4General
Itisrecommendedthatinstallationofoutdoorunitsbecontractedtoaprofessional
installer
Beforeworkingonequipmentconnectedtopowerlinesortelecommunicationlines,
removejewelryoranyothermetallicobjectthatmaycomeintocontactwithenergized
parts
Useextremecar ewheninstallingantennasnearpowerlines
Useextremecar ewhenworkingatheights
WhenusinganACpowersourceforRADWINdevices,alwaysusetheACpoweradapter
suppliedbyRADWIN
Usetherighttools!
DonotmountanODUupsidedownorhorizontally.Doingthismayvoidyouproduct
warranty.
4.2.5InternalESDProtectioncircuits
RADWINequipmentisdesignedtomeettheETSI/FCC/Aus/NZ/CSAEMCandSafety
requirements.Tofulfilltheserequirements,thesystem'sTelecomlinesattheODU/PoEare
TransformerisolatedandincludeinternalESD(ElectroStaticDischarge)Protectioncircuits.