Digital Modules
3-32
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
3.9.4 Interrupts of the SM 321; DI 16 x 24 VDC
Introduction
This section describes the SM 321; DI 16 x 24 VDC with regard to its interrupt
behavior. The following interrupts exist:
Diagnostic interrupt
Hardware interrupt
The OBs and SFCs mentioned below can be found in the online Help for STEP 7,
where they are described in greater detail.
Enabling interrupts
The interrupts are not preset – in other words, they are inhibited without
appropriate parameter assignment. Assign parameters to the Interrupt Enable in
STEP 7 (refer to Section 3.9.2).
Diagnostic interrupt
If you have enabled diagnostic interrupts, then active error events (initial
occurrence of the error) and departing error events (message after
troubleshooting) are reported by means of an interrupt.
The CPU interrupts the execution of the user program and processes the
diagnostic interrupt block (OB 82).
In the user program, you can call SFC 51 or SFC 59 in OB 82 to obtain more
detailed diagnostic information from the module.
The diagnostic information is consistent until such time as OB 82 is exited. When
OB 82 is exited, the diagnostic interrupt is acknowledged on the module.
Hardware interrupt
The SM 321; DI 16 x 24 VDC can trigger a hardware interrupt for every channel
group with a rising or falling edge, or both, of a signal status change.
Perform parameter assignment one channel group at a time. It can be modified at
any time (in RUN mode using the user program).
Pending hardware interrupts trigger hardware interrupt processing in the CPU
(OB 40). The CPU interrupts the execution of the user program or of the priority
classes with low priority.
You can set in the user program of the hardware interrupt OB (OB 40) how the
programmable logic controller has to react to an edge change. When the hardware
interrupt OB is exited, the hardware interrupt is acknowledged on the module.
The module can buffer one interrupt per channel. If no higher priority run-time
levels are waiting to be processed, the buffered interrupts (of all modules) are
serviced one after the other by the CPU according to the order in which they
occurred.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals