Reading out diagnostic messages
You can read out detailed diagnostic messages by means of SFCs in the user
program (refer to the Appendix “Diagnostic Data of Signal Modules”).
You can view the cause of the error in STEP 7, in the module diagnosis (refer to
online Help for STEP 7).
Diagnostic message in the measured value of analog input modules
Every analog input module supplies the measured value 7FFF
H
irrespective of the
parameter assignment when an error is detected. This measured value means
either Overflow, Malfunction or a channel is disabled.
Diagnostic message by means of SF LED
Every analog module indicates errors for you by means of your SF LED (group
error LED). The SF LED lights as soon as a diagnostic message is triggered by the
analog module. It goes out when all errors have been rectified.
Diagnostic messages of the analog input modules
The table below gives an overview of the diagnostic messages for the analog input
modules.
Table 4-46 Diagnostic Messages of the Analog Input Modules
Diagnostics Message
LED Diagnostics
Effective for
Parameters can
be assigned
External auxiliary supply missing SF Module No
Configuring/parameter assignment
error
SF
Channel Yes
Common-mode error SF Channel Yes
Wire-break SF Channel Yes
Underflow SF Channel Yes
Overflow SF Channel Yes