Digital Modules
3-96
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
3.28 Relay Output Module SM 322; DO 8 x Rel. 230 VAC;
(6ES7322-1HF01-0AA0)
Order number
6ES7322-1HF01-0AA0
Characteristics
The SM 322; DO 8 x REL. 230 VAC features the following characteristics:
8 outputs, isolated in groups of 2
Rated load voltage 24 VDC to 120 VDC, 48 VAC to 230 VAC
Suitable for AC/DC solenoid valves, contactors, motor starters, fractional h.p.
motors and indicator lights.
Behavior upon power down of the supply voltage
Note
Applicable only for the SM 322; DO 8 x Rel. 230 VAC with product status 1 is:
When the power supply is switched off, the capacitor still stores energy for about
200 ms. The relay can therefore still be driven briefly within this time by the user
program.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)