A-28
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Temperature measurement
The table below contains the codes for the different temperature measurements,
which you enter in byte 0 of data record 1 (refer to Figure A-12).
Table A-19 Codes for temperature measurement of the analog input module
Temperature unit for linearization
Code
Degrees Celsius 2#0000 0000
Degrees Fahrenheit 2#0000 1000
Kelvin 2#0001 0000
Interference frequency suppression
The table below contains the codes for the different frequencies, which you enter in
byte 1 of data record 1 (refer to Figure A-12). You must work out the resulting
integration time separately for each module!
Table A-20 Codes for Interference Suppression of the Analog Input Module
Interference Suppression
Integration Time Code
60 Hz 50 ms 2#01
50 Hz 60 ms 2#10
Measuring methods and measuring ranges
The table below contains all the measuring methods and measuring ranges of the
analog input module and their codes. You must enter these codes in bytes 2 to 13
of data record 1 (refer to Figure A-12).
Note
Please note that the analog input module must be wired in accordance with the
measuring range and at the front connector correspondingly!
Table A-21 Codes for the Measuring Ranges of the Analog Input Module
Measuring
Method
Code Measuring Range Code
Deactivated 2#0000 Deactivated 2#0000
Voltage 2#0001 " 50 mV
" 500 mV
" 1 V
" 5 V
1 to 5 V
0 to 10 V
" 10 V
2#1011
2#0011
2#0100
2# 0110
2#0111
2#1000
2#1001